Bentel J424-8 Control panel 8-24 zones

327,33  / 640,20 lv.

Main
Quantity per set: 1
In addition
Product Type FireClass J400 Conventional Control Panel
Importer: PROFESSIONAL PROTECTION – ELECTRONICS LTD
EN54 and EN12094-1 certificates

Course: 1 EUR = 1.95583 BGN SKU: 295 Categories: ,
Description

Designed and manufactured to EN54 and EN12094-1 standards (with J400-EXT extinguishing module), the J424-8 is a microprocessor-based control panel for medium and large applications.

It has an 8-zone motherboard and supports two J400-EXP8 expansion modules, for a total of 24 zones and 512 devices (a maximum of 32 in each zone). Each zone is equipped with an alarm repeater for selective alarm control in the event of a fire.

The control panel has monitored and non-monitored alarm outputs for controlling self-powered sirens, piezoelectric sirens, fire bells, flashing beacons, auto-diallers, etc.

This easy-to-use control panel is protected by a lockable front plate, allowing operational access only to authorised personnel.

The J424 control panel is also available with a display that shows all information regarding the status of the control panel. The optional Console software in a Windows™ environment allows for full management of event logs, files, resets, and all programmable functions provided by the control panel.

EN54 and EN12094-1 approved (with extinguishing module J400-EXT)
8 supervised, balanced input zones, which can be bypassed, expandable to 24 using two 8 zone expanders
Up to 32 devices can be connected to each zone (but no more than 512 in total): conventional fire detectors, alarm buttons, gas detectors
Gas zone compatible with 4 – 20 mA gas sensors
Manual signal point recognition
Programmable thresholds
Missing sensors
Day/night mode
Time to check the alarm
Programmable recovery and reset times
One output for alarm repeat (open collector) for each input zone
2 observed, resettable, bypassable 24V alarm outputs for controlling piezoelectric sirens, fire bells and flashing beacons
Disabling, bypassing alarm output for activation of 24V sirens with their own power supply
Disabling fault warning output for activating signalling and supplementary devices
Monitored fire exit for telephone dialler activation
Programmable open-collector output
Alarm/fault memory until next reset
Signal disabling command (sirens)
Command security using key and code
Programmable from computer or keyboard
Memory for 50 computer-visible events
Optional backlit display
RS485 bus for connecting up to 4 repeater panels
Technical specifications

Power supply: 230 Vac ±10%
27.6 Vdc 2.5 A switched-mode power supply/battery charger
Space for two 12Vdc 17Ah batteries
Dimensions (W x H x D): 422x502x116 millimetres
Weight (excluding batteries): max. 8.5 kg.

Additional information
Weight1 kg
Manufacturer