FCFIRERAY-ONE – Beam detector/Optical beam smoke detector
1 369,08 € / 2 677,69 lv.
Technical Information
Fireray One Parameters Minimum Typical Maximum Unit
Operating Voltage 14 – 36 V
Operating Current 4.5 5.0 5.5 mA
Operating Current – Alignment Modes 31 33 35 mA
Response Thresholds (25%, 35%, 55%, 85%) 1.25 1.87 8.24 dB
(note – only the 25% and 35% are EN54-12-approved) 25 35 85 %
Delay to Alarm – 10 – seconds
Delay before fault - 10 - s
Operating Distance (Separation between Detector and 5 – 120 m
Reflector) (4 reflectors required for >50m, >164ft) 16 394 feet
Rapid Obscuration Fault Threshold – 85 – %
Maximum angular alignment range of detector – – ±4.5 Degrees
Tolerance to beam misalignment (per EN54-12) – Detector – ±0.5 – degrees
Tolerance to beam misalignment (per EN54-12) – Reflector – ±5 – Degrees
Optical Wavelength – 850 – nm
Operating Temperature -20 – +55 °C
-4 – +131 °F
Storage Temperature -40 – +85 °C
-40 – +185 °F
Relative Humidity (non-condensing) – – 93 %RH
IP rating – 55 – –
Fire & Fault Relays (VFCO, Resistive) – Contact voltage – – 30 V DC
Fire & Fault Relays (VFCO, Resistive) – Contact current – 2 A
Cable gauge 22 – 14 AWG
0.5 – 1.6 mm
Classe de inflamabilidade do alojamento – UL940 V0 –
Fireray One Dimensions and Weights Width (mm) Height (mm) Depth (mm) Weight (kg)
Reflective Detector, including smart base 134 182 151 0.7
Reflector 100 100 10 0.1
Additionally
Description No special tools or knowledge is required for installation and operation. Fireray One is a standalone beam detector with easy installation. Using Fireray One, you get the benefits of a beam detector in your applications.
Product type: Reflective optical beam smoke detector
Importer PROFESSIONAL PROTECTION – ELECTRONIC Ltd.
| Weight | 1 kg |
|---|